Setting FLUIDWELL Pump Pressure Display

FLUIDWELL F053-A (Pressure Monitor with High/ Low Pressure Alarms) 

Figure 1.1 - Fluidwell F053-A

On the pump pressure display, set the following parameters as listed per the manufacturers instructions, usually using for Single Pump on Oilfield Services;

For PRESSURE:
- Set UNIT parameter to PSI
- Set DECIMALS parameter to 00000
- Set SPAN to 15000 (or max range of PSI xdcr)
- Set OFFSET to 0

For ALARM (OPKO):
- Set PRESSURE ZERO to IGNORE
- Set ALARM LOW to 0
- Set ALARM HIGH to desired kick out pressure
- Set DELAY ALARM LOW to 0 (or lowest value)
- Set DELAY ALARM HIGH to 0 (or lowest value)
- Set ALARM OUTPUT to HIGH

For DISPLAY:
- Set SET ALARM to OPERATOR
- Set BARGRAPH to ON (if present)
- Set BACKLIGHT to OFF (or GREEN/ AMBER)

For POWERMAN:
- Set LCD NEW to FAST
- Set BATTMODE to OPERA
 
For SENSOR:
- Set FORMULA to INTERPOLATION
- Set FILTER to 0
- Set CUTOFF to 0.0
- Set CALIBRATE LOW to CALIBRATE (this will zero the meter to the actual zero pressure output of the transmitter – do this only while the sensor is connected and unit is not operating).

  • For Details, download Operation Manual here.