Setting FLUIDWELL Pump Rate Display

FLUIDWELL F012-P (Rate/ Totalizer)

On the pump rate display, set the following parameters as listed per the manufacturers instructions, usually using for Single Pump on Oilfield Services;
Figure 1.1 - Fluidwell F012-P


For TOTAL:
- Set UNIT parameter to bbl
- Set DECIMALS parameter to 111111.1
- Set K-FACT to 5554.430 for plunger size 4.5in FE*
- Set K-FACT dECS to 0

*This is calculated by the formula:
(#MPU TEETH X DRIVELINE RPM) / BPM, with values taken from the pump schedule.

For FLOWRATE:
- Set UNIT parameter to bbl
- Set TIME parameter to MIN
- Set DECIMALS parameter to 111111.1
- Set K-FACT to 5554.430 for 4.5in FE*
- Set K-FACT dECS to 0
- Set CALCULATE parameter to 1
- Set CUT-OFF to 0.1 

For DISPLAY:
- Set FUNCTION to TOTAL
- Set BACKLIGHT to OFF (or GREEN/ AMBER)

For POWERMAN:
- Set LCD NEW to FAST
- Set BATTMODE to OPERATE

For FLOWMETER:
- Set SIGNAL to NPN LP
  • For Details, download User Manual here.