AUDIBLE ALARM: GAGE NOT RESPONDING on Murphy PowerView Display

GAGE NOT RESPONDING

Figure 1.1 - Audible Alarm (Gage Not Responding)

Faults and Warnings
The PowerView provides two means for detecting Faults and Warnings: visual LEDs on the casing and Fault indicators on the display.

#Visual Indication:
  • Amber LED (Warning)
  • Red LED (Derate/ Shutdown)

#Fault Indicators: Auxiliary Gage Fault
Murphy’s PVA (PowerView Analog) Gages can be attached to the PowerView. If an Auxiliary Gage should fail, the 1-up or 4-up display will be replaced with the Fault message "GAGE NOT RESPONDING" (Refer to Figure 1.1 above). NOTE: The Fault can only be cleared by correcting the cause of the Fault condition.

PVA Gages not working
When PVA Gages are connected and do not seem to work, go to the UTILITIES menu and select REMOVE ALL GAGES.
Figure 1.2 - Utilities
UTILITIES is the last item on the Main Menu. The Utilities menu provides troubleshooting features and other information about the PowerView configuration.

Figure 1.3 - Remove All Gages
→GAGE DATA - View data for optional connected PVA gages.
→REMOVE ALL GAGES - Reset the gage memory on the PowerView.
→SOFTWARE VERSION - This screen lists Configuration, Firmware, Languages, and Bootloader versions for this PowerView unit.
→FAULT CONVERSION - View/ Edit the J1939 Fault code version.
→ANALOG INPUT - With Analog Input highlighted, press Enter. You can select between two settings: BACKLIGHT DIMMER and FUEL LEVEL.
→ENGINE SPEED CONTROL - This option must be ON in the OEM Menu for functionality to be available from the Utilities Menu.

Figure 1.4 - Clearing Gages