DSE3110 Deep Sea Electronics: DSE Configuration Suite PC Software
DSE3110 Module
DSE 3110 for HARTECH HT-500D Genset (500 kVA)
Figure 1.1 - DSE 3110 MPU v2.2 |
#Replace new DSE3110 display:
(1). Using the PC Configuration Suite PC Software (Opening page)
→When no updates are available and when available updates are complete, the initial start-up screen is
displayed. Free download here.
→The screen prompts the user to select between the three main uses for the software:
• Creating a new configuration. Select the module type under Create new configuration.
• Editing a previously saved configuration. Select the configuration file either from the Open
recent configuration area or by clicking Open a configuration file and browsing to the file.
• Reading the configuration of a connected module. Click Read configuration from a module.
The file is read from a currently connected controller and is available for editing in the
Configuration Suite.
Figure 1.3 - Read configuration from a module |
(2). Screen Layout
Figure 1.4 - Screen Layout DSE3110 |
→Module Option: This section allows the user to change the options related to the module's operation.
Figure 1.5 - Module (Module Option) |
Lamp Test at Power-Up = Illuminates all module LEDs at startup
Power Save Mode Enable = Module is placed into low current power save mode after one minute of inactivity in
STOP mode.
Protected Start Enable = Manual mode is entered upon the first press of the Start Button. A further press is
required to start the Engine. This helps prevent inadvertent starting of the set by users
pressing the button by mistake.
Power up in AUTO mode = The module enters AUTO mode when DC power is first applied.
Display Voltages Phase to Phase = The module displays the measured voltage multiplied by 2 or by "root 3" as required by
the AC System selected.
(b). Application
→Engine Options: Allows selection of the Engine type
being used (ie Conventional Diesel
Engine, Gas Engine or Electronic
Engine).
Figure 1.6 - Engine Options (Conventional Engine) |
(c). Digital Inputs: The Digital Inputs page is subdivided into smaller sections.
Select the required section with the mouse.
→Digital Input A-C
Figure 1.7 - Digital Inputs (A-C) |
• User Configured = Allows the user to set how the inputs reacts when active (typically used
to give an alarm signal to the controller from an external protection
device).
• Remote Start Off Load = If this input is active, operation will be similar to the "Remote Start On Load" function except that the generator will not be instructed to take the load. This function can be used where an Engine only run is required e.g. for exercise.
→Output A, Output B, Output C, and Output D - These labels
match the
typical wiring
diagram.
-Click Yes on message box: Write this configuration?
→Wait the Progress bar until 100%, and click OK.
• Alternative Configuration = Used to instruct the module to use the settings in the "alternative" configuration.
• Coolant Temperature Switch = This input is used to give a Coolant Temperature High shutdown from a
digital normally open or closed switch.
• Emergency Stop = Used to give a signal from the Emergency Stop switch to give
immediate shutdown of the Engine. It is also recommended that the
emergency stop switch breaks the signal from the Fuel and Start
outputs or ECU Power outputs as applicable.
• External Panel Lock = Used to lock the module into the current operating mode (ie STOP or
AUTO mode).
• Low Fuel Level Switch = A digital normally open or closed fuel level switch gives this input to
trigger a warning alarm.
• Oil Pressure Switch = A digital normally open or closed oil pressure switch gives this input.
→Digital Input D-F
Figure 1.8 - Digital Inputs (D-F) |
• Remote Start On Load = When in AUTO mode, the module will perform the start sequence and
transfer load to the generator.
In Manual mode, the load will be transferred to the generator if the Engine is already running, however in manual mode, this input will not
generate start/stop requests of the Engine.
• Smoke Limiting = This input instructs the module to give a run at idle speed command to
the Engine either via an output configured to smoke limit or by data
commands when used with supported electronic Engines.
#Polarity: Close or open to activate.
#Action: Select the type of
alarm required: Electrical Trip, Shutdown, and Warning.
#Arming: Configures when the
input is active:
Never, Always, Active
from starting (From Starting), Active
from the end of the
safety timer (From Safety On).
(d). Outputs
→Digital Outputs
Figure 1.9 - Digital Outputs |
→Output Sources
#Source: Select what the output is to be used to control.
• Not Used = The output will not change state (Unused).
• Close Gen Output = Used to control the load switching device.
Whenever the 3110 module selects the
generator to be on load this control source
will be active.
• Charge Alternator Alarm
• Close Gen Output Pulse = Used to control the load switching device. Whenever the 3110 module selects the
generator to be on load this control source will be active for the duration of the Breaker
Close Pulse timer, after which it will become inactive again.
• Common Alarm = Active when one or more alarms (of any
type) are active.
• Common Shutdown = Active when one or more Shutdown alarms
are active.
• Common Warning = Active when one or more Warning alarms
are active.
• Energise to Stop = Normally used to control an Energise to Stop
solenoid, this output becomes active when
the controller wants the set to stop running.
• Fuel Relay = Becomes active when the controller requires
the governor/fuel system to be active.
• Open Gen Output = Used to control the load switching device.
Whenever the 3110 module selects the
generator to be off load this control source
will be active.
• Open Gen Output Pulse = Used to control the load switching device. Whenever the 3110 module selects the
generator to be off load this control source will be active for the duration of the Breaker
Open Pulse timer, after which it will become inactive again.
• Under Voltage Shutdown = Click to enable or
disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled (IEEE 37.2 - 27AC Undervoltage relay).
• Under Frequency Shutdown = IEEE 37.2 -81 Frequency relay.
• Preheat During Preheat Timer = Becomes active when the preheat timer
begins.
Normally used to control the Engine preheat
glow-plugs.
• Preheat Until End of Cranking = Becomes active when the preheat timer
begins.
Normally used to control the Engine preheat
glow-plugs.
• Preheat Until End of Safety Timer = Becomes active when the preheat timer
begins.
Normally used to control the Engine preheat
glow-plugs.
• Preheat Until End of Warming Timer = Becomes active when the preheat timer
begins.
Normally used to control the Engine preheat
glow-plugs.
• Smoke Limiting = Becomes active when the controller requests
that the Engine runs at idle speed.
As an output, this can be used to give a
signal to the Idle input of an Engine speed
governor (if available).
• Start Relay = Active when the controller requires the cranking of the Engine.
(e). Timers
→Many timers are associated with alarms. Where this occurs, the timer for the alarm is located on the same page as the alarm setting. Timers not associated with an alarm are located on the timers page.
Figure 2.1 - Timers |
#Start Timers
• Start Delay = Used to give a delay before starting in AUTO mode. This timer is activated upon a remote start
signal being applied, or upon a start due to mains failure, scheduled run or any other automatic
start.
Typically this timer is applied to prevent starting upon fleeting remote start signals or short term
mains failures.
• Pre-heat = Give a "pre-start" time during which the Preheat output will become active (if configured).
• Smoke Limiting = The amount of time that the Engine will be requested to run at idle speed upon starting. This is
typically used to limit emissions at startup.
• Smoke Limiting Off = This should be set to a little longer than the amout of time that the set takes to run up to rated
speed after removal of the command to run at idle speed. If this time is too short, the set could
be stopped due to underspeed failure. If the time is too long, underspeed protection is disabled
until the Smoke limit time off time has expired.
• Warming = The amount of time that the set will run BEFORE being allowed to take load. This is used to
warm the engine to prevent excessive wear.
#Stopping Timers
• Return Delay = A delay, used in auto mode only, that allows for short term removal of the request to stop the set
before action is taken. This is usually used to ensure the set remains on load before accepting
that the start request has been removed.
• Cooling = The amount of time that the set will be made to run OFF LOAD before being stopped. This is to
allow the set to cool down and is particularly important for engines with turbo chargers.
• ETS Solenoid Hold = The amount of time the Energise to stop solenoid will be kept energised after the Engine has
come to rest. This is used to ensure the set has fully stopped before removal of the stop solenoid
control signal.
#Breaker
• Breaker Trip Pulse = The amount of time that Breaker Open Pulse signals will be present when the request to open a
breaker is given.
• Breaker Close Pulse = The amount of time that Breaker Close Pulse signals will be present when the request to close a
breaker is given.
#Alternator
(f). Generator
The generator page is subdivided into smaller sections.
Select the required section with the mouse.
→Generator Options
Figure 2.2 - Generator Options |
• Alternator Fitted = There is no alternator in the system, it is an Engine only application. Or an alternator is fitted to the Engine, it is a generator application.
• Poles = The number of poles on the alternator
• AC System = Allows a number of AC systems to be catered for. Although the 3110 module has
only a two-wire input, rated to 277V nominal (absolute maximum 305V), it is
possible to use the module with different systems as long as the maximum rating is
not exceeded.
Selecting the AC system shows the connections required for that particular system,
along with the relevant connection numbers on the controller.
→Generator Voltage
Figure 2.3 - Generator Voltage Alarms |
• Over Voltage Shutdown = IEEE 37.2 - 59AC Overvoltage relay.
→Generator Frequency
Figure 2.4 - Generator Frequency Alarms |
• Over Frequency Shutdown = IEEE 37.2 -81 Frequency relay.
(g). Engine
The engine page is subdivided into smaller sections.
Select the required section with the mouse.
• Engine Options
→Engine Options: This item is not
adjustable here, it’s
read only. To
change this item,
visit the module
menu.
Figure 2.5 - Engine Options |
Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.
→Crank Disconnect
Figure 2.6 - Crank Disconnect |
Crank disconnect settings are used to detect when the set fires during the starting sequence.
As the set is cranked, the first parameter that passes it’s crank disconnect setting will result in the cessation of
the cranking signal.
Having more than one crank disconnect source allows for a much faster crank disconnect response leading to
less wear on the engine and starter components, and provides added safety in case one source is lost, by a
blown or tripped fuse for example.
#Options
• Crank Disconnect on Oil Pressure = Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.
• Check Oil Pressure Prior to Starting = If check oil pressure prior to
starting is enabled, the cranking
will not be allowed if the oil
pressure is not seen as being
low. This used as a double check
that the Engine is stopped before
the starter is engaged.
#Crank Disconnect
• Generator Frequency = Click and drag to change the
setting.
• Engine Speed = Type the value
or click the up
and down
arrows to
change the
settings.
→Speed Settings
• Under Speed Shutdown = Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.
• Over Speed Shutdown = Type the value
or click the up
and down
arrows to
change the
settings.
(h). Alternative Configuration
Figure 2.7 - Configuration Options |
The Alternative Configuration is provided to allow the system designer to cater for different AC requirements
utilising the same generator system. Typically this feature is used by Rental Set Manufacturers where the set
is capable of being operated at (for instance) 120V 50Hz and 240V 50Hz using a selector switch, or by taking
advantage of the “auto voltage sensing” option of the DSE3110 Series.
Alternative configuration options contain a subset of the main configuration. The adjustable parameters are
not discussed here as they are identical to the main configuration options.
#Additional Note:
DSE3110 Data Sheet - download here.
DSE3110 Operator Manual - download here.
DSE3110 Installation Instructions - download here.
DSE Configuration Suite Software Installation Manual - download here.
Write to Module
Write the currently open configuration settings to the module by click the Write to Module button.
Figure 2.8 - Write to Module |
Figure 2.9 - Progress |
Howdy Guys
ReplyDeleteIf you are in searching of Legit vendor for Fullz you are at right place
Just try my stuff you'll never be disappointed
Although, I'm giving replacement for the bad stuff as well
USA UK CANADA Fresh Fullz Info Pros Leads Available
All States & Cities info are available
Young Age, Old age, Mid age,, Every age you can asked
Real DL scan with selfie proof available
Fullz Pros with dl issue & Expiry dates available as well
Each & Every type of Fullz Pros Leads of USA UK CANADA you can get from my shop
Samples are also available for bulk buyers & for testing
No scam, will show you proof of everything as well
Contact me for the best deals & discounts
24/7 available for you
What's App - +1.. 7277.. 886.. 129..
Tele - @ leadsupplier & @ killhacks
Skype - @ peeterhacks
E mail - cyber.zoneuniverse at g mail . com
Fresh Spammed available in Thousands & Millions
Stuff will be provided within 10 mins after payment proof
Guarantee for the stuff Info & Validity
USA SSN DOB DL ADDRESS EMPLOYEE & BANK INFO FULLZ LEADS
UK NIN DOB DL ADDRESS SORT CODE ACCOUNT NUMBER FULLZ
CANADA SIN DOB DL MMN PHONE EMAIL FULLZ
DL SCAN ORIGINAL FRONT & BACK WITH SELFIE
BUSINESS EIN COMPANY FULLZ
OLD & YOUNG AGE PROS
STUDENTS PROS IN BULK
HIGH CREDIT SC PROS FULLZ 700+
FULLZ WITH SSN DL MVR
DL FULLZ WITH ISSUE & EXP DATES
EMAIL & PHONE NUMBER & BANK INFO LEADS USA UK CANADA
CC WITH CVV & DUMPS WITH PINS
CARDING & CASH OUT METHODS WITH TUTORIALS
SPAM-MMING TUTORIALS WITH TOOLS & LEADS
OFFICE365 LEADS & LOGINS
Quantity with Quality stuff available
Payment only in Crypto & Cash app
Thanks for the overview on DSE3110 and the DSE Configuration Suite! It's great to see how this software simplifies the configuration of Deep Sea controllers.
ReplyDelete